- Library Home /
- Search Collections /
- Open Collections /
- Browse Collections /
- UBC Theses and Dissertations /
- Identification of weak nodes in power systems
Open Collections
UBC Theses and Dissertations
UBC Theses and Dissertations
Identification of weak nodes in power systems Dehnel, Morgan P.
Abstract
This thesis describes a method for determining weak nodes in power systems which may cause divergence in Newton-Raphson loadflow methods. When divergence occurs in production loadflow programs, information related to the cause of divergence is not available. The "Weak Node Method" of this thesis provides such information by identifying one or more weak nodes. The development of the Weak Node Method required extensive experimentation with the Newton-Raphson method. The behaviour of the vectors and matrices of the Newton-Raphson method during divergence are discussed in an effort to familiarize the reader with observed trends. These trends suggested the techniques which comprise the Weak Node Method. With this method, a "quasi" solution is sought first, and, secondly, three analysis procedures are then used to pinpoint the weak nodes. The method was tested using three test cases which would normally have caused the Newton-Raphson loadflow method to diverge.
Item Metadata
Title |
Identification of weak nodes in power systems
|
Creator | |
Publisher |
University of British Columbia
|
Date Issued |
1987
|
Description |
This thesis describes a method for determining weak nodes in power systems which may cause divergence in Newton-Raphson loadflow methods.
When divergence occurs in production loadflow programs, information related to the cause of divergence is not available. The "Weak Node Method" of this thesis provides such information by identifying one or more weak nodes.
The development of the Weak Node Method required extensive experimentation with the Newton-Raphson method. The behaviour of the vectors and matrices of the Newton-Raphson method during divergence are discussed in an effort to familiarize the reader with observed trends.
These trends suggested the techniques which comprise the Weak Node Method. With this method, a "quasi" solution is sought first, and, secondly, three analysis procedures are then used to pinpoint the weak nodes. The method was tested using three test cases which would normally have caused the Newton-Raphson loadflow method to diverge.
|
Genre | |
Type | |
Language |
eng
|
Date Available |
2010-07-20
|
Provider |
Vancouver : University of British Columbia Library
|
Rights |
For non-commercial purposes only, such as research, private study and education. Additional conditions apply, see Terms of Use https://open.library.ubc.ca/terms_of_use.
|
DOI |
10.14288/1.0097176
|
URI | |
Degree | |
Program | |
Affiliation | |
Degree Grantor |
University of British Columbia
|
Campus | |
Scholarly Level |
Graduate
|
Aggregated Source Repository |
DSpace
|
Item Media
Item Citations and Data
Rights
For non-commercial purposes only, such as research, private study and education. Additional conditions apply, see Terms of Use https://open.library.ubc.ca/terms_of_use.